Altronix AL1024ULXB2 Installation Instructions User Manual

Browse online or download User Manual for Accessories for electrical Altronix AL1024ULXB2 Installation Instructions. Altronix AL1024ULXB2 Installation Instructions User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Agency Listings:
• ULRecognizedcomponentforAccessControl
SystemUnits(UL294),PowerSuppliesfor
FireProtectiveSignalingSystems(UL1481).
Input:
• Input115VAC/60Hz,4.2amp.
Output:
• 24VDCoutput(UL1481).
• 8ampcontinuoussupplycurrentwith10amp
supplycurrentduringalarm.
• 24VDC@10amp.(UL294).
• Filteredandelectronicallyregulatedoutput.
• MaximumRipple:250mVP/P
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
Battery Backup (cont’d):
• Maximumchargecurrent3.6amp.
• Automaticswitchovertostand-bybattery
whenACfails.
• Zerovoltagedropwhenswitchedovertobatterybackup.
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatteryandbatterypresencesupervision
(form“C”contacts).
Additional Features:
• Shortcircuitandthermaloverloadprotection.
Board Dimensions (W x L x H approximate):
4.5”x8.4”x1.9”(114.427mmx213.36mmx49.657mm)
Stand-by Specifications:
Output
15 min. of Stand-by &
5 min. of Alarm
4 hr. of Stand-by &
5 min. of Alarm
24 hr. of Stand-by &
5 min. of Alarm
60 hr. of Stand-by &
5 min. of Alarm
24VDC/12AH
Battery
Stand-By=8amp
Alarm=10amp
Stand-By=1.5amp
Alarm=10amp
Stand-By=200mA
Alarm=10amp
Stand-By=100mA
Alarm=10amp
Output
15 min. of Stand-by &
5 min. of Alarm
4 hr. of Stand-by &
5 min. of Alarm
24 hr. of Stand-by &
15 min. of Alarm
60 hr. of Stand-by &
15 min. of Alarm
24VDC/65AH
Battery
-----------------------------------------------
Stand-By=8.0amp
Alarm=10amp
Stand-By=1.5amp
Alarm=10amp
Stand-By=500mA
Alarm=10amp
Installation Instructions:
TheAL1024ULXB2shouldbeinstalledinaccordancewitharticle760ofTheNationalElectricalCodeaswellas
NFPA72andallapplicableLocalCodes.
1. MounttheAL1024ULXB2inthedesiredlocation/enclosure.
2. ConnectunswitchedACpower(115VAC60Hz)totheterminalsmarked[L,N](Fig. 1, pg. 2).Use14AWGorlarger
forallpowerconnections(Battery,ACinput,DCoutput).Use22AWGto18AWGforpower-limitedcircuits
(ACFail/LowBatteryreporting).
Keep power-limited wiring separate from non power-limited wiring
(115VAC / 60Hz Input, Battery Wires). DC output Minimum 0.25” spacing must be provided.
3. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
4. Connectdevicestobepoweredtotheterminalsmarked[+DC--](Fig. 1, pg. 2).
5. ForAccessControlapplicationsbatteriesareoptional.Whenbatteriesarenotused,alossofACwillresultinthe
lossofoutputvoltage.Whentheuseofstand-bybatteriesisdesired,theymustbeleadacidorgeltype.Connect
batterytoterminalsmarked[--BAT+](Fig. 1, pg. 2).
6. ItisrequiredtoconnectappropriatesignalingnotificationdevicestoACFAIL&BATFAIL(Fig. 1, pg. 2)
supervisoryrelayoutputs.Use22AWGto18AWGwires.ACFAILwillreportin5minutes.
Todelayreport6hourscut“ACDelay”jumper(Fig. 1a, pg. 2).
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel.
Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged,checkspecifiedvoltagebothat
batteryterminalandattheboardterminalsmarked[--BAT+]toensurethereisnobreakinthebatteryconnectionwires.
Note:Maximumchargingcurrentunderdischargeis3.6amp.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
AL1024ULXB2 - UL Recognized
Power Supply/Charger Rev.082312
Overview:
TheAL1024ULXB2isapowersupplythatconvertsa115VAC/60Hzinput,toa24VDCnonpower-limitedoutput
(seespecifications).
Specifications:
Page view 0
1 2

Summary of Contents

Page 1 - AL1024ULXB2 - UL Recognized

Agency Listings:• ULRecognizedcomponentforAccessControl SystemUnits(UL294),PowerSuppliesfor FireProtectiveSignalingSystems(UL1481)

Page 2 - Terminal Identification:

LED Diagnostics:Red (DC) Green (AC) Power Supply StatusON ON Normaloperatingcondition.ON OFF LossofAC,Stand-bybatterysupplyingpower.OFF ON No