Altronix SMP10PM Installation Instructions User Manual

Browse online or download User Manual for Accessories for electrical Altronix SMP10PM Installation Instructions. Altronix SMP10PM Installation Instructions User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Overview:
The SMP10PM is a supervised power supply that converts a low voltage AC input into 12VDC or 24VDC output with a
10 amp continuous supply current.
Specifications:
Voltage Output/Transformer Selection Table:
Output VDC Switch Position Transformer
12VDC @ 10 amp SW1 - Closed 24VAC or 28VAC / 175VA (Altronix model T2428175)
24VDC @ 6 amp SW1 - Open 24VAC or 28VAC / 175VA (Altronix model T2428175)
24VDC @ 10 amp SW1 - Open 24VAC or 28VAC / 300VA (Altronix model T2428300)
Installation Instructions:
The SMP10PM should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the SMP10PM in the desired location/enclosure.
2. Set the SMP10PM to the desired DC output voltage by setting the switches (Fig. 1a, pg. 2) to the
appropriate positions (Voltage Output/Transformer Selection Table).
3. Connect proper transformer to the terminals marked [AC] (refer to Voltage Output/Transformer Selection Table).
Use 18 AWG or larger for all power connections (Battery, DC output).
Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered to the terminals marked [+ DC -].
6. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to the terminals
marked [+ BAT -] on the board (battery leads included). Use two (2) 12VDC batteries connected in series for
24VDC operation.
Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
7. Connect appropriate trouble reporting devices to AC Fail & Low battery supervisory
relay outputs marked [NC, C, NO]. Use 22 AWG to 18 AWG for AC Fail / Low Battery reporting.
AC Failure will report in 5 minutes. For a 6 hour delay on reporting cut resistor R1.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition
ON OFF Loss of AC, Stand-by battery supplying power
OFF ON No DC output
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output
SMP10PM
Supervised Power Supply/Charger
Input:
• Input28VAC.
(Voltage Output/Transformer Selection Table).
Output:
• 12VDCor24VDCselectableoutput.
• 10ampsupplycurrent.
• Filteredandelectronicallyregulatedoutputs.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Maximumchargecurrent0.7amp.
• Zerovoltagedropwhenswitchingovertobatterybackup.
Supervision:
• ACfailsupervision(form“C”contacts).
• Batterypresenceandlowbatterysupervision
(form“C”contacts).
Indicators:
• ACinputandDCoutputLEDindicators.
Board Dimensions (W x L x H approximate):
7.045”x4.266”x2.127”
(178.95mm x 109.36mm x 54.05mm).
Page view 0
1 2

Summary of Contents

Page 1

Overview:The SMP10PM is a supervised power supply that converts a low voltage AC input into 12VDC or 24VDC output with a 10 amp continuous supply curr

Page 2 - Terminal Identification:

Terminal Identification:Terminal Legend Function/DescriptionAC/ACLow voltage AC input (Voltage Output/Transformer Selection Table).For 12VDC output us