Altronix MAXIMAL55 Datasheet

Browse online or download Datasheet for Power distribution units (PDUs) Altronix MAXIMAL55. Altronix MAXIMAL55 power distribution unit PDU User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Maximal55
Access Power Controller
Rev. DSMaximal55 - F27K
This unit distributes and switches power to access control systems and
accessories. They convert a 115VAC 60Hz input into sixteen (16) independently
controlled 12VDC fuse protected outputs. These Fail-Safe/Fail-Secure power
outputs may be converted to dry form “C” contacts. The outputs are activated by an
open collector sink or normally open (NO) dry trigger input from an Access Control
System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of
access control hardware devices including: Mag Locks, Electric Strikes, Magnetic
Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm
Monitoring, or may be used to trigger other auxiliary devices. The fire alarm
disconnect feature is individually selectable for any or all of the sixteen (16) outputs.
All interconnecting equipment must be UL Listed.
Overview
12VDC output.
Maximum output current:
12VDC @ 19 amp.
Options P/S 1 P/S 2
A 12VDC @ 9.5 amp 12VDC @ 9.5 amp
115VAC 60Hz, 6.0 amp input.
Input fuse rated @ 3.5 amp/250V.
Power supply input options:
a) Two (2) common power input for either ACM8
and lock power (factory installed).
b) Two (2) isolated power inputs (external power
supply is required), (current is determined by the
power supply connected, not to exceed a
maximum of 10 amp total).
Sixteen (16) Access Control System trigger inputs.
Input options:
a) Sixteen (16) normally open (NO) inputs.
b) Sixteen (16) open collector inputs.
c) Any combination of the above.
Sixteen (16) independently controlled outputs.
Output options:
a) Sixteen (16) Fail-Safe and/or Fail-Secure
power outputs.
b) Sixteen (16) form “C” 5 amp rated relay outputs.
c) Any combination of the above.
Sixteen (16) auxiliary power outputs (unswitched)
(outputs are rated 2.5 amp).
ACM8 boards main fuse is rated at 10 amp.
Output fuses are rated @ 3.5 amp.
Red LEDs indicate outputs are triggered
(relays energized).
Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
sixteen (16) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry
contact input.
b) Polarity reversal input from FACP signaling circuit.
Alarm output relay indicates that FACP input is
triggered (form “C” contact rated @ 1 amp 28VDC).
Green LED indicates FACP disconnect is triggered.
Filtered and electronically regulated outputs (built-in
power supply).
Built-in charger for sealed lead acid or gel type
batteries.
Maximum charge current 0.7 amp.
Automatic switch over to stand-by battery when
AC fails.
Zero voltage drop when unit switches over to battery
backup (AC failure condition).
Thermal and short circuit protection with auto reset.
AC input and DC output LED indicators.
AC fail supervision (form “C” contact).
Low battery and battery presence supervision
(form “C” contact).
Enclosure accommodates up to four (4)
12AH batteries.
Maximal55 weights (approximate):
Product weight: 39.95 lbs.
Shipping weight: 43.95 lbs.
Maximal55
Specifications
Page view 0
1 2

Summary of Contents

Page 1 - Access Power Controller

Maximal55Access Power ControllerRev. DSMaximal55 - F27KThis unit distributes and switches power to access control systems andaccessories. They convert

Page 2 - Agency Approvals

 AltronixCorp.-14058thStreet,Brooklyn,NY11220•718-567-8181•888-258-7669•altronix.comEnclosure Dimensions (approximate)26”H x 19”W x 6.2

Comments to this Manuals

No comments