Altronix AL1012ULACM Datasheet

Browse online or download Datasheet for Power extensions Altronix AL1012ULACM. Altronix AL1012ULACM power extension User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
AL1012ULACM
Eight (8) independently controlled
fuse protected outputs.
AL1012ULACMCB
Eight (8) independently controlled
PTC protected outputs.
Class 2 Rated power limited outputs.
The AL1012ULACM / AL1012ULACMCB converts an 115VAC 60Hz input
into eight (8) independently controlled 12VDC Fail-Safe and/or Fail-Secure
outputs with a total of 10 amp continuous supply current. Outputs are
activated by an open collector sink or normally open (NO) dry trigger input
from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc.
These units will route power to a variety of access control hardware devices
including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The
outputs will operate in both Fail-Safe and/or Fail-Secure modes. The units are
designed to be powered by one common power source (factory installed)
which will provide power for both the board operation and locking devices,
or two (2) totally independent power sources, one (1) providing power for
board operation and the other for lock / accessory power. The FACP Interface
enables Emergency Egress, Alarm Monitoring, or may be used to trigger
other auxiliary devices. The fire alarm disconnect feature is individually
selectab
le for any or all of the eight (8) outputs.
12VDC @ 10 amp supply current.
Power supply input options:
a) One (1) common power input for ACM8/
ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8/ACM8CB and one (1) for lock
accessory power, (external power supply
is required). (Cur
rent is determined b
y the
power supply connected, not to exceed a
maximum of 10 amp total).
Eight (8) Access Control System trigger inputs.
Input options:
a)
Eight (8) nor
mall
y open (NO) inputs.
b)
Eight (8) open collector inputs.
c)
Any combination of the above.
Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure
power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs
(AL1012ULACM only).
c) Any combination of the above.
Eight (8) auxiliary power outputs (unswitched)
Output ratings:
- Fuses are rated @ 3.5 amp (AL1012ULACM).
- PTCs are rated @ 2.5 amp (AL1012ULA
CMCB).
Input 115VAC 60Hz rated @ 1.9 amp.
ACM8 board main fuse is rated at 10 amp.
Filtered and electronically regulated outputs
(built-in power supply).
Short circuit and ther
mal o
verload protection.
Red LEDs indicate outputs are triggered (relays energized).
Fire Alarm disconnect (latching or non-latching) is
individuall
y selectab
le for any or all of the
eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP
signaling circuit.
Alarm output relay indicates that FACP input
is triggered (form “C” contact rated @ 1 amp 28VDC
not evaluated by UL).
Green LED indicates when FACP disconnect
is triggered.
Built-in char
ger for sealed lead acid or
gel type batteries.
AL1012ULXB (Power Supply Board)
maximum char
ge cur
rent .7 amp.
Automatic switch over to stand-by battery
when AC fails.
Zero voltage drop when unit switches over to battery
backup (AC failure condition).
AC fail supervision (form "C" contact).
Battery fail and battery presence supervision
(form "C" contact).
AC input and DC output LED indicators.
Enclosure accommodates up to tw
o (2) 12AH batteries.
Product w
eight:
- AL1012ULACM: 10.2 lbs.
- AL1012ULACMCB: 9.8 lbs.
Shipping weight:
- AL1012ULACM: 11.5 lbs.
- AL1012ULACMCB: 11.1 lbs.
AL1012ULACM, AL1012ULACMCB
Power Supply/Chargers w/Multi-Output
Access Power Controllers Rev. DSAL1012ULACM - A25F
Overview
Specifications
Page view 0
1 2

Summary of Contents

Page 1 - AL1012ULACM, AL1012ULACMCB

AL1012ULACM• Eight (8) independently controlledfuse protected outputs.AL1012ULACMCB• Eight (8) independently controlledPTC protected outputs.• Class 2

Page 2 - Agency Approvals

Enclosure Dimensions15.5”H x 12”W x 4.5”D4.50"4.50"4.50"1.25"2.13"2.25"3.38"3.38"1.25"4.50" 1.50&quo

Comments to this Manuals

No comments