Rev. 042010AL802ULADAJNAC Power ExtenderInstallation Guide(See Application Guide for additional information)
- 10 - AL802ULADAJAppendix A - UL Listed Compatible DevicesA.1 Four (4) Wire Smoke DetectorsTable A-1 below lists four (4) wire smoke detectors compat
AL802ULADAJ - 11 -A.1 Four (4) Wire Smoke Detectors (cont.)Smoke Detector/BaseDetector TypeMax StandbyCurrent (mA)AlarmCurrent (mA)System Sensor 4W-B
- 12 - AL802ULADAJ1.50"1.25"2.50"6.00"2.50"1.50"2.50"1.50"1.00"1.50"1.00"1.50"2.75"4.
- 2 - AL802ULADAJAgency Listings:• UL Listed Control Units for Fire Protective Signaling Systems (UL 864). • MEA - NYC Department of Buildings Approv
AL802ULADAJ - 3 -Power Supply Specifications:Stand-by Specifications:Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain batter
- 4 - AL802ULADAJNote: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with synchronization capability.7. For conn
AL802ULADAJ - 5 -Note: It is required to control visual notification appliances (strobes) via input 1 [IN1] and audible notification appliances (horns
- 6 - AL802ULADAJTerminal Identification Table:AL800ADA Power Supply Board**Power Board Parameter Specifications:• AC Fail condition will report appro
AL802ULADAJ - 7 -NC NO CAC LocalFuseCoverBattery 2Battery connection (non power limited)CAUTION: De-energize unit prior to servicing. For continued p
- 8 - AL802ULADAJOptional hookups:1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to rep
AL802ULADAJ - 9 -Battery Calculation WorksheetUnits are capable of recharging 40 AH battery max. If total ampere - hour required exceeds 40 AH,decreas