MADE IN USA
LGN
--- BAT +
Open - 24V
Closed - 12V
SW1
DC
PTC2
VR1
AC
--- DC +
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
O
N ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal Function/Description
Legend
L, G, N Connect 115 VAC to these terminals:
Black to Hot, White to Neutral, Green to ground.
+ DC - 12VDC @ 1.2 amp continuous supply current.
24VDC @ .5 amp continuous supply current.
- BAT + Stand-by battery connections. Maximum charge rate .3 amp.
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime
Warranty, Made in U.S.A.