Rev. 052313AL1042ULADANAC Power ExtenderInstallation Guide(See Application Guide for additional information)Altronix Corp.140 58th St. Brooklyn, NY
- 10 - AL1042ULADAAppendix A - UL Listed Compatible DevicesA.1 Four (4) Wire Smoke DetectorsTableA-1belowlistsfour(4)wiresmokedetectorscompat
AL1042ULADA - 11 -A.1 Four (4) Wire Smoke Detectors (cont.)Smoke Detector/BaseDetector TypeMax StandbyCurrent (mA)AlarmCurrent (mA)SystemSensor4W-
- 12 - AL1042ULADAAltronixisnotresponsibleforanytypographicalerrors.14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9
- 2 - AL1042ULADAAgency Listings:• ULListedforControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuilding
AL1042ULADA - 3 -Power Supply Specifications:AC Input:120VAC60Hz,5amp,suppliedbyamaximum15ampdedicatedbranchcircuit.Output:Four(4)regul
- 4 - AL1042ULADA6. ConnectFACPoutputtothedesiredAL842LGKlogicboardinputs,andnotificationappliancestothedesiredAL842LGK logicboar
AL1042ULADA - 5 -Amount of Notification Appliances per NAC:Amseco 27perNAC* SystemSensor® 32perNAC*Faraday 39perNAC* CooperWheelock® 32perNA
- 6 - AL1042ULADATerminal Identification Table:Power Supply BoardTerminal Legend Function/DescriptionL,N Connect120VACtotheseterminals:LtoHo
AL1042ULADA - 7 -NEC Power-Limited Wiring Requirements for AL1042ULADA Models:Power-limitedandnonpower-limitedcircuitwiringmustremainseparate
- 8 - AL1042ULADAOUT1 OUT2 OUT3 OUT4INP2 INP1 FAULTRESETOUT1 OUT3OUT2OUT4IN>OUT SYNCSTROBE SYNCTEMPORALINPUT SELECT IN>OUT SYNCSTROBE SYNCTEM
AL1042ULADA - 9 -Battery Calculation WorksheetDeviceNumber of DevicesCurrent per DeviceStand-by CurrentAlarm CurrentForeachdeviceusethis