Altronix AL125ULX Installation Instructions User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
VR1
NO NOGND GND FA CP1 FAC P2 STRIKE+
COM-- LOCK+
+ AUX --
TRIG
INPUT
RESET
SW1
+ BAT --
XFMR
SW2:
12VDC - Open
24VDC - Closed
XFMR
115VAC
50/60 Hz,
.6 amp
Blue Lead
Ye llow Lead
White
Lead
Black
Lead
Green
Lead
(ground)
STEP 1:
Use these holes to mount
AL125ULB b
y pushing the nylon
circuit board f
asteners
(Fig
. 1A)
through the back of the enclosure.
Nylon fasteners will snap into place.
(Fig. 1A)
Nylon Fastener
STEP 2:
Mount AL125ULB circuit board to nylon
f
asteners by pressing down circuit board onto
nylon fasteners.
Note: Springlock on fasteners is used to remove
AL125ULB circuit board.
Note: Four (4) nylon fasteners are
provided in the AL125ULB carton.
Springlock
Fig. 1 - Board Installation Diagram:
Note:
- AL125UL, AL125ULX - Connect blue and yellow
leads of transformer to terminals marked [XFMR]
on the power supply board.
- AL125ULP, AL125ULE - Connect 24VAC @ 40VA
from UL Listed plug-in transformer to the terminals
marked [XFMR]on the power supply board.
VR1
NO NOGND GND
FACP1 FA CP2
STRIKE+
COM-- LOCK+
+ AUX --
TRIG
INPUT
RESET
SW1
+ BAT --
XFMR
SW2:
12VDC - Open
24VDC - Closed
Normal Open
Access Control
Triggering
Device
Normal Open
Reset Device
2.2K EOL
(supplied)
MAG LOCK
NC
FACP
NO
FACP
{ }
Card
Reader
Fig. 2 - Application Diagram:
LED Diagnostics:
Red Power Supply Status
ON Normal function.
OFF No DC output.
Slow Blink Loss of AC.
Rapid Blink Unit is triggered, awaiting reset. Fire alarm interface activated.
Fig. 2A - SW1
OPEN SWITCH
CLOSED SWITCH
ELECTRIC
STRIKE
STRIKE+
LOCK+
Com-
- 3 -
Page view 2
1 2 3 4

Comments to this Manuals

No comments