AL1002ULADA - 3 -
Power Supply Specifications:
AC Input:
120VAC60Hz,5amp.
Output:
Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.
One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervised
totaloutputcurrentmustnotexceedcurrent10ampinAlarmCondition.
Battery:
Usetwo(2)12VDC/12AHortwo(2)12VDC/7AHbatteriesconnectedinseries.
Stand-by/Alarm Current
Consumption:
130mA/300mA
EOL Resistor
(end of line):
2.2K(2200ohm),AltronixModel#AL-EOL22(included).
Ground fault maximum
test impedance:
1000ohm.
Stand-by Specifications:
Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output
24VDC/7AH 24Hours 10amp/5minutes ---
24VDC/12AH
(usetwo(2)12VDCbatteriesinseries)
24Hours 10amp/5minutes 50mA
24VDC/36AH 24Hours 10amp/5minutes 1amp
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When
loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 10 amp total
alarm current (example: AUX = 1 amp, outputs up to 9 amp).
Installation Instructions:
WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA
72/ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.
Productisintendedforindooruseonly.
Carefully review:
Application Guide for AL602ULADA, AL802ULADA, AL1002ULADA
Power Supply Specifications (pg. 3)
Stand-by Specifications (pg. 3)
Output Programming Selection Table (pg. 4)
Sync Mode Selection Table (pg. 4)
Terminal Identification Table (pgs. 5-6)
LED Status Indication Table (pg. 6)
1.Mountunitinthedesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholes
intheenclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placethe
enclosure’supperkeyholesoverthetwoupperscrews,levelandsecure.Markthepositionofthelowertwoholes.
Removetheenclosure.Drillthelowerholesandinstallthetwofasteners.Placetheenclosure’supperkeyholesover
thetwoupperscrews.Installthetwolowerscrewsandmakesuretotightenallscrews
(Enclosure Dimensions, pg. 12).
2. Connectgreenleadtoearthground (Fig 1).Connecttheline(L)andneutral(N)terminalstoaseparateunswitched
ACcircuit(120VAC,60Hz)dedicatedtotheFireAlarmSystem.
3. Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
4. Connectbatterytotheterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded).
Note:IfbatteriesbeingusedinyourinstallationdonotfitintotheAL1002ULADAunit,itisrequiredtoinstalla
separateenclosure,ULListedforappropriateapplication.Separatebatteryenclosureisrequiredtohave50cubicinches
ofadditionalopenspace.AllwiringmethodsshallbeinaccordancewiththeNationalElectricalCodeNFPA70/
NFPA72/ANSIandwithalllocalcodesandauthoritieshavingjurisdiction.Batterycircuitsarenotpower-limited;
provide0.25”spacingfrompower-limitedcircuitsanduseseparateknockout.Ifadditionalbatteryenclosure
isrequired,itmustbeULListedfortheapplicationandmountedwithin5’oftheAL1002ULADAenclosureinthe
sameroom;minimum12AWGwireinappropriateconduitisrequiredforconnection.Whenusingconduit,make
sureitisinstalledinamatterwhereitcannotturn.
5. Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2]and
desiredoutputsignaltype (Output Programming Selection Table, pg. 4).
L N
line
ground
neutral
Fig. 1