- 8 - AL1002ULADA
Optional hookups:
1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to
reportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional
supervisorymonitoring.
ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 3a, Pg. 8)tothe
commontroubleinput.
2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman
addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule).
Connection to triggering devices must be made within 20ft. of distance and using conduit for wiring.
3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.
4- ACLocal[NC,NO,C]shouldconnecttothehostcontrolpanelforlocalannunciationof
thetroublecondition.
Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe
shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 3b, Pg. 8).
Optional Hookup Diagram:
Fig. 3
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel
(26.2-26.4VDC recommended range).
Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltage
bothatbatteryterminalandattheboardterminalsmarked[+BAT--]toensurethatthereisnobreakinthebattery
connectionwires.
Fuses:Checkinputandoutputfusesonthepowersupplyboard,replaceifnecessary.Inputfuseratingis6.3amp@
250V,Outputfuseratingis15amp@32V.
Note:Maximumchargingcurrentis1.5amp.
Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.
These circuits are used to monitor AC and
Bat Fail and will cause a simultaneous trouble
condition to the FACP's IN1 and IN2 (Non-Supervised)
4-wire Smoke
Detector
+
--
+
--
4-wire Smoke
Detector
Fire Alarm
Control Panel
(FACP)
EOL Power
Supervision Relay
(Not Supplied)
EOL
Resistor
from FACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NC C NO C "FAULT" NC
OUT1 OUT3
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+
IN1--
IN2--
IN2+
C "DRY1" NC
RET1+
RET1--
RET2--
RET2+
C "DRY2" NC
+ OUT2 --
+ OUT3 --
+ OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
-- AUX +
UPPER TERMINALS
LOWER TERMINALS
Addressable Control
Module Trigger Output
See Note 2
(Non-Supervised)
RESET
Supervised
Non-Supervised
Input from
Power Supply
BAT FAIL
AC FAIL
DC AC
AC DELAY
NC C NO NC C NO
AC LOCAL
NC C NO
L
N
6.3A 250V
Digital Communicator
or Local Annunciator
Dry output Contact
(Form "C" contacts)
Power-Limited Outputs
2.5 amp per output in alarm
Total = 10 amp
(Supervised)
AC FAIL
NC C NO
BAT FAIL
NC C NO
Fig. 3a
-- DC +
OUT1 OUT3
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
RESET
Fig. 3c
TroubleMemory
ResetButton
Fig. 3b
Common
trouble
Input/Output
NC CNOC "FAULT" NC
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12

Comments to this Manuals

No comments