Rev. 042010AL802ULADANAC Power ExtenderInstallation Guide(See Application Guide for additional information)Altronix Corp.140 58th St. Brooklyn, NY
- 10 - AL802ULADAAppendix A - UL Listed Compatible DevicesA.1 Four (4) Wire Smoke DetectorsTableA-1belowlistsfour(4)wiresmokedetectorscomp
AL802ULADA - 11 -A.1 Four (4) Wire Smoke Detectors (cont.)Smoke Detector/BaseDetector TypeMax StandbyCurrent (mA)AlarmCurrent (mA)SystemSensor4W
- 12 - AL802ULADAEnclosure Dimensions:15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)MEMBERAltronixisnotresponsibleforanytypographicalerror
- 2 - AL802ULADA Agency Listings:• ULListedControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildi
AL802ULADA - 3 -Power Supply Specifications:AC Input:120VAC60Hz,5amp,suppliedbyamaximum15ampdedicatedbranchcircuit.Output:Four(4)regu
- 4 - AL802ULADAClass A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:• ForallClassB,StyleW,X,Y,hookupsSW1&SW2ontheAL
AL802ULADA - 5 -Amount of Notification Appliances per NAC:Amseco 27perNAC*SystemSensor® 32perNAC*Faraday 39perNAC*CooperWheelock® 32perNAC
- 6 - AL802ULADATerminal Identification Table:AL800ADA Power Supply Board*Terminal Legend Function/DescriptionL,G,N Connect120VACtotheseter
AL802ULADA - 7 -These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2Digi
- 8 - AL802ULADAOptional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]
AL802ULADA - 9 -Battery Calculation WorksheetUnitsarecapableofrecharging40AHbatterymax.Iftotalampere-hourrequiredexceeds40AH,decreas